Overall Reset By Means Of The Siemens Simatic Manager; Actions After A Memory Reset; Firmware Update - YASKAWA CPU 013C Manual

For vipa system slio
Table of Contents

Advertisement

Deployment CPU 013-CCF0R00

Firmware update

4.12.2

Overall reset by means of the Siemens SIMATIC Manager

Proceeding
4.12.3

Actions after a memory reset

Activating functionality by
means of a VSC
Automatic reload
Reset to factory setting
4.13
Firmware update
Overview
Current firmware at
www.vipa.com
80
For the following proceeding you must be online connected to your CPU.
1.
For an overall reset the CPU must be switched to STOP state. You may place the
CPU in STOP by the menu command 'PLC è Operating mode'.
2.
You may request the overall reset by means of the menu command 'PLC
è Clean/Reset'.
ð A dialog window opens. Here you can bring your CPU in STOP state, if not
already done, and start the overall reset. During the overall reset procedure the
STOP-LED flashes. When the STOP-LED is on permanently the overall reset
procedure has been completed.
If there is a VSC from VIPA plugged, after an overall reset the according functionality is
automatically activated.
If there is a project S7PROG.WLD on the memory card, after an overall reset the CPU
attempts to reload this project from the memory card. ® The SD LED is on. When the
reload has been completed the LED expires. The operating mode of the CPU will be
STOP respectively RUN, depending on the position of the operating mode switch.
The Reset to factory setting deletes completely the internal RAM of the CPU and resets
this to delivery state. Please regard that the MPI address is also set back to default 2!
Ä Chapter 4.14 'Reset to factory settings' on page 82
There is the opportunity to execute a firmware update for the CPU and its components
via memory card. For this an accordingly prepared memory card must be in the CPU
during the start-up. So a firmware files can be recognized and assigned with start-up, a
pkg file name is reserved for each update-able component and hardware release, which
begins with "px" and differs in a number with 6 digits. The pkg file name of every update-
able component can be found at a label on the module. The SLIO CPU has no label.
Here the pkg file name can be shown via the web page. After PowerON and operating
mode switch in STOP position, the CPU checks if there is a *.pkg file at the memory card.
If this firmware version is different to the existing firmware version, this is indicated by
blinking of the LEDs and the firmware may be installed by an update request.
The latest firmware versions can be found in the service area at www.vipa.com. For
example the following files are necessary for the firmware update of the CPU 013-
CCF0R00 and its components with hardware release 01:
n
CPU 013C, Hardware release 01: Px000265.pkg
Ä 'VSD' on page 84