Deployment CPU 013-CCF0R00
Setting standard CPU parameters > Parameter CPU
Retentive Memory
Interrupts
Time-of-day interrupts
Cyclic interrupts
68
n
Size of the process image input/output area
Here the size of the process image max. 2048 for the input/output periphery may
be fixed (default: 256).
n
OB85 call up at I/O access error
The preset reaction of the CPU may be changed to an I/O access error that
occurs during the update of the process image by the system.
The VIPA CPU is preset such that OB 85 is not called if an I/O access error
occurs and no entry is made in the diagnostic buffer either.
n
Clock memory
Activate the check box if you want to use clock memory and enter the number of
the memory byte.
The selected memory byte cannot be used for temporary data storage.
n
Number of Memory bytes from MB0
Enter the number of retentive memory bytes from memory byte 0 onwards.
n
Number of S7 Timers from T0
Enter the number of retentive S7 timers from T0 onwards. Each S7 timer occu-
pies 2bytes.
n
Number of S7 Counters from C0
Enter the number of retentive S7 counter from C0 onwards.
n
Areas
This parameter is not supported.
n
Priority
Here the priorities are displayed, according to which the hardware interrupt OBs
are processed (hardware interrupt, time-delay interrupt, async. error interrupts).
n
Priority
This value is fixed to 2.
n
Active
By enabling 'Active' the time-of-day interrupt function is enabled.
n
Execution
Select how often the interrupts are to be triggered.
Intervals ranging from every minute to yearly are available. The intervals apply to
the settings made for start date and time.
n
Start date/time
Enter date and time of the first execution of the time-of-day interrupt.
n
Process image partition
This parameter is not supported.
n
Priority
Here the priorities may be specified according to which the corresponding cyclic
interrupt is processed.
Execution
n
Enter the time intervals in ms, in which the watchdog interrupt OBs should be pro-
cessed.
The start time for the clock is when the operating mode switch is moved from
STOP to RUN.