VIPA System SLIO

7.6 Fast introduction

Overview
Steps of configuration

7.7 Hardware-Konfiguration

Overview
HB300 | CPU | 013-CCF0R00 | en | 16-40
Never choose an IP address with Host-ID=0 or Host-ID=maximum! (e.g.
for class B with subnet mask = 255.255.0.0, the "172.16.0.0" is reserved
and the "172.16.255.255" is occupied as local broadcast address for this
network.)
At the first commissioning respectively after an overall reset with PowerON again of the
CPU, the Ethernet PG/OP channel has no IP address. This can only be reached by its
MAC address. By means of the MAC address, which is printed at the front as 'MAC PG/
OP:...' , you can assign IP address data. The assignment takes place directly via the
hardware configuration of the Siemens SIMATIC Manager.
For the configuration of the Ethernet PG/OP channel for productive connections please
follow the following approach:
n
Hardware configuration - CPU
n
Hardware configuration - Ethernet PG/OP channel
n
Configure connections
Siemens S7 connections
(Configuration via Siemens NetPro, communication via VIPA handling blocks)
Open communication
(Configuration and communication happens by standard handling blocks)
n
Transfer of the complete project to CPU
In the Siemens SIMATIC Manager, the CPU 013-CCF0R00 from VIPA is
to be configured as CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)!
The Ethernet PG/OP channel of the CPU 013-CCF0R00 is always to be
configured as CP343-1 (343-1EX30 V3.0) from Siemens at slot 4.
At the first commissioning respectively after an overall reset with PowerON again of the
CPU, the Ethernet PG/OP channel has no IP address. This can only be reached by its
MAC address. By means of the MAC address, which is printed at the front as 'MAC PG/
OP:...' , you can assign IP address data. The assignment takes place directly via the
hardware configuration of the Siemens SIMATIC Manager.
CPU
n
Ä Chapter 4.4 'Hardware configuration - CPU' on page 61
n
Ethernet PG/OP channel
Ä Chapter 4.6 'Hardware configuration - Ethernet PG/OP channel' on page 64
Deployment PG/OP communication - productive
Hardware-Konfiguration
177