YASKAWA CPU 013C Manual page 132

For vipa system slio
Table of Contents

Advertisement

Deployment I/O periphery
Frequency measurement > SFB 48 - FREQUENC - Frequency measurement
Name
Declaration
JOB_REQ
INPUT
JOB_ID
INPUT
JOB_VAL
INPUT
STS_GATE
OUTPUT
MEAS_VAL
OUTPUT
JOB_DONE
OUTPUT
JOB_ERR
OUTPUT
JOB_STAT
OUTPUT
Local data only in instance DB
Name
Data type
JOB_OVAL
DINT
Frequency meter request
interface
Proceeding
Name
Data type
JOB_REQ
BOOL
JOB_ID
WORD
JOB_VAL
DINT
132
Data type
Address
(Inst.-DB)
BOOL
4.3
WORD
6.0
DINT
8.0
BOOL
12.0
DINT
14.0
BOOL
22.0
BOOL
22.1
WORD
24.0
Address
(Instance DB)
28.0
Per channel you may call the SFB in each case with the same instance
DB, since the data necessary for the internal operational are stored here.
Writing accesses to outputs of the instance DB is not permissible.
To read/write the registers of the frequency meter the request interface of the SFB 48
may be used.
So that a new job may be executed, the previous job must have be finished with
JOB_DONE = TRUE.
The deployment of the request interface takes place at the following sequence:
Edit the following input parameters:
Address
Default
(DB)
4.3
FALSE
6.0
0
8.0
0
Default value
Comment
FALSE
Initiates the job (edge 0-1)
0
Job ID
0
Value for write jobs
FALSE
Status of the internal gate
0
Evaluated frequency
TRUE
New job can be started.
FALSE
Job error
0
Job error ID
Default
Comment
-
Output value for read request.
Comment
Initiates the job (edges 0-1)
Job ID:
00h Job without function
04h Writes the integration time
84h Read the integration time
Value for write jobs.
Permitted value for integration time:
10 ... 10000ms
HB300 | CPU | 013-CCF0R00 | en | 16-40
VIPA System SLIO

Advertisement

Table of Contents
loading

This manual is also suitable for:

013-ccf0r00

Table of Contents