VIPA System SLIO
Diagnostics/Clock
Protection

4.7.3 Parameter for MPI/DP

HB300 | CPU | 013-CCF0R00 | en | 16-40
n
Phase offset
Enter the delay time in ms for current execution for the watch dog interrupt. This
should be performed if several watchdog interrupts are enabled.
Phase offset allows to distribute processing time for watchdog interrupts across
the cycle.
n
Process image partition
This parameter is not supported.
n
Report cause of STOP
Activate this parameter, if the CPU should report the cause of STOP to PG
respectively OP on transition to STOP.
n
Number of messages in the diagnostics buffer
This parameter is ignored. The CPU always has a diagnostics buffer (circular
buffer) for 100 diagnostics messages.
n
Synchronization type
Here you specify whether clock should synchronize other clocks or not.
as slave: The clock is synchronized by another clock.
as master: The clock synchronizes other clocks as master.
none: There is no synchronization
n
Time interval
Time intervals within which the synchronization is to be carried out.
n
Correction factor
Lose or gain in the clock time may be compensated within a 24 hour period by
means of the correction factor in ms.
If the clock is 1s slow after 24 hours, you have to specify a correction factor of
"+1000" ms.
n
Level of protection
Here 1 of 3 protection levels may be set to protect the CPU from unauthorized
access.
Protection level 1 (default setting):
No password adjustable, no restrictions
Protection level 2 with password:
Authorized users: read and write access
Unauthorized user: read access only
Protection level 3:
Authorized users: read and write access
Unauthorized user: no read and write access
The properties dialog of the MPI(PtP) interface X3 is opened via a double click to the sub
module MPI/DP
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
ment storage media - VSD, VSC' on page 83
Deployment CPU 013-CCF0R00
Setting standard CPU parameters > Parameter for MPI/DP
Ä Chapter 4.15 'Deploy-
69