4.4 Hardware configuration - CPU

Precondition
Installing the IO device
VIPA SLIO System
HB300 | CPU | 013-CCF0R00 | en | 16-40
Up to 64 SLIO modules can be connected to a SLIO CPU. This sum includes power and
clamp modules.
You may access the modules with read res. write accesses to the peripheral bytes or the
process image. To define addresses a hardware configuration may be used. For this,
click on the properties of the according module and set the wanted address.
If you do not like to use a hardware configuration, an automatic addressing is established.
Here the address assignment follows the following specifications:
n
Starting with slot 1, the central plugged modules are assigned with ascending logical
addresses.
n
The length of the memory area corresponds to the size of the process data of the
according module. Information about the sizes of the process data can be found in
the according manual of the module.
n
The memory areas of the modules are assigned without gaps separately for input and
output area.
n
Digital modules are mapped starting at address 0 and all other modules are mapped
starting from address 256. ETS modules are mapped starting from address 256.
n
As soon as the mapping of digital modules exceeds the address 256, by regarding
the order, these are mapped starting from address 256.
n
The configuration of the CPU takes place at the Siemens 'hardware configurator' .
The hardware configurator is part of the Siemens SIMATIC Manager. It serves for
project engineering.
n
Please use for configuration the Siemens SIMATIC Manager V 5.5 SP2 and up.
n
The configuration of the System SLIO CPU happens in the Siemens SIMATIC Man-
ager by means of a virtual PROFINET IO device 'VIPA SLIO CPU' . The 'VIPA SLIO
System' is to be installed in the hardware catalog by means of the GSDML.
For project engineering a thorough knowledge of the Siemens SIMATIC
Manager and the Siemens hardware configurator is required!
The installation of the PROFINET IO devices 'VIPA SLIO CPU' happens in the hardware
catalog with the following approach:
1.
Go to the service area of www.vipa.com.
2.
Load from the download area at 'PROFINET files' the file System SLIO_Vxxx.zip.
3.
Extract the file into your working directory.
4.
Start the Siemens hardware configurator.
5.
Close all the projects.
6.
Select 'Options è Install new GSD file'
7.
Navigate to your working directory and install the according GSDML file.
ð After the installation according PROFINET IO device can be found at
'PROFINET IO è Additional field devices è I/O è VIPA SLIO System'
Deployment CPU 013-CCF0R00
Hardware configuration - CPU