VIPA System SLIO
Connection types
Siemens S7 connection
Combination options with deployment of the FB/SFB VIPA handling blocks
Connection partner
specified in NetPro
(in the current project)
unspecified in NetPro
(in the current project)
unspecified in NetPro
(in the unknown project)
HB300 | CPU | 013-CCF0R00 | en | 16-40
With this CPU exclusively Siemens S7 connection may be configured with Siemens
NetPro.
n
For data transfer with Siemens S7 connections the FB/SFB VIPA handling blocks are
necessary; the deployment is described in the manual "Operation list" of your CPU.
n
At Siemens S7 connections the communication connections are specified by a con-
nection ID for each communication partner.
A connection is specified by the local and partner connection end point.
n
At Siemens S7 connections the TSAPs must be congruent crosswise. The following
n
parameters define a connection end point:
The following parameters define a connection end point:
Station A
remote TSAP
local TSAP
ID A
Connection establishing
active/passive
active
passive
active/passive
Deployment PG/OP communication - productive
à
Siemens
S7 connection
ß
Connection
specified
specified
unspecified
specified (connection name in an other
project)
Configure Siemens S7 connections
Station B
à
local TSAP
ß
remote TSAP
ID B
181