Hardware Configuration - Ethernet Pg/Op Channel - YASKAWA CPU 013C Manual

For vipa system slio
Table of Contents

Advertisement

Deployment CPU 013-CCF0R00

Hardware configuration - Ethernet PG/OP channel

4.6 Hardware configuration - Ethernet PG/OP channel
Overview
Assembly and commis-
sioning
"Initialization" via PLC
functions
64
The CPU 013-CCF0R00 has an integrated Ethernet PG/OP channel. This channel allows
you to program and remote control your CPU.
n
The Ethernet PG/OP channel (X1/X2) is designed as switch. This enables PG/OP
communication via the connections X1 and X2.
The PG/OP channel also gives you access to the internal web page that contains
n
information about firmware version, connected I/O devices, current cycle times etc.
n
With the first start-up respectively after an overall reset the Ethernet PG/OP channel
does not have any IP address.
n
For online access to the CPU via Ethernet PG/OP channel valid IP address parame-
ters have to be assigned to this. This is called "initialization".
n
This can be done with the Siemens SIMATIC Manager.
1.
Install your System SLIO with your CPU.
2.
Wire the system by connecting cables for voltage supply and signals.
3.
Connect the one of the Ethernet jacks (X1, X2) of the Ethernet PG/OP channel to
Ethernet.
4.
Switch on the power supply.
ð After a short boot time the CP is ready for communication. He possibly has no
IP address data and requires an initialization.
The initialization via PLC functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your Ethernet PG/OP channel.
This can be found at the front of your CPU with the name "MAC PG/OP: ...".