Configuration with TIA Portal
TIA Portal - Hardware configuration - Ethernet PG/OP channel
Take IP address parame-
ters in project
224
7.
Confirm with [Assign IP configuration].
ð Directly after the assignment the Ethernet PG/OP channel is online reachable
using the set IP address data. The value remains as long as it is reassigned, it
is overwritten by a hardware configuration or an factory reset is executed.
Due to the system you may get a message that the IP address could not
be assigned. This message can be ignored.
1.
Open your project.
2.
If not already done, configure in the 'Device configuration' a Siemens CPU 314C-2
PN/DP (314-6EH04-0AB0 V3.3).
3.
As Ethernet PG/OP channel place at slot 4 the Siemens CP 343-1 (6GK7
343-1EX30 0XE0 V3.0).
4.
Open the "Property" dialog by clicking on the CP 343-1EX30 and enter for the CP at
"Properties" at "Ethernet address" the IP address data, which you have assigned
before.
5.
Transfer your project.
VIPA System SLIO
HB300 | CPU | 013-CCF0R00 | en | 16-40