YASKAWA CPU 013C Manual page 48

For vipa system slio
Table of Contents

Advertisement

Hardware description
Technical data
Order no.
Initial data size
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)
Total current per group, horizontal configuration, 40°C
Total current per group, horizontal configuration, 60°C
Total current per group, vertical configuration
Output voltage signal "1" at min. current
Output voltage signal "1" at max. current
Output current at signal "1", rated value
Output current, permitted range to 40°C
Output current, permitted range to 60°C
Output current at signal "0" max. (residual current)
Output delay of "0" to "1"
Output delay of "1" to "0"
Minimum load current
Lamp load
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
Actuation of digital input
Switching frequency with resistive load
Switching frequency with inductive load
Switching frequency on lamp load
Internal limitation of inductive shut-off voltage
Short-circuit protection of output
Trigger level
Number of operating cycle of relay outputs
Switching capacity of contacts
Output data size
Technical data analog inputs
Number of inputs
Cable length, shielded
48
013-CCF0R00
16 Bit
12
1000 m
600 m
DC 24 V
ü
20 mA
6 A
6 A
6 A
L+ (-0.8 V)
L+ (-0.8 V)
0.5 A
5 mA to 0.6 A
5 mA to 0.6 A
0.5 mA
2 µs / 30 µs
3 µs / 175 µs
-
10 W
not possible
ü
max. 1000 Hz
max. 0.5 Hz
max. 10 Hz
L+ (-45 V)
yes, electronic
1 A
-
-
12 Bit
2
200 m
HB300 | CPU | 013-CCF0R00 | en | 16-40
VIPA System SLIO

Advertisement

Table of Contents
loading

This manual is also suitable for:

013-ccf0r00