YASKAWA CPU 013C Manual page 223

For vipa system slio
Table of Contents

Advertisement

VIPA System SLIO
"Initialization" via Online
functions
Assign IP address param-
eters
HB300 | CPU | 013-CCF0R00 | en | 16-40
4.
Switch on the power supply.
ð After a short boot time the CP is ready for communication. He possibly has no
IP address data and requires an initialization.
The initialization via the Online functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your Ethernet PG/OP channel.
This can be found at the front of the CPU labelled as "MAC PG/OP: ...".
You get valid IP address parameters from your system administrator. The assignment of
the IP address data happens online in the Siemens TIA Portal with the following pro-
ceeding:
1.
Start the Siemens TIA Portal.
2.
Switch to the 'Project view' .
3.
Click in the 'Project tree' at 'Online access' and choose here by a doubleclick your
network card, which is connected to the Ethernet PG/OP channel.
4.
To get the stations and their MAC address, use the 'Accessible device' . This can
be found at the front of the CPU labelled as "MAC PG/OP: ...".
5.
Choose from the list the module with the known MAC address (Onboard PG/OP
[MAC address]) and open with "Online & Diagnostics" the diagnostics dialog in the
Project area.
6.
Navigate to Functions > Assign IP address. Type in the IP configuration like IP
address, subnet mask and gateway.
TIA Portal - Hardware configuration - Ethernet PG/OP channel
Configuration with TIA Portal
223

Advertisement

Table of Contents
loading

This manual is also suitable for:

013-ccf0r00

Table of Contents