YASKAWA CPU 013C Manual page 108

For vipa system slio
Table of Contents

Advertisement

Deployment I/O periphery
Counting > SFB 47 - COUNT - Counter controlling
Proceeding
Name
Data type
JOB_REQ
BOOL
JOB_ID
WORD
JOB_VAL
DINT
*) State remains set also after a CPU STOP-RUN transition.
Name
Data type
JOB_DONE
BOOL
JOB_ERR
BOOL
JOB_STAT
WORD
108
The deployment of the request interface takes place at the following sequence:
1.
Edit the following input parameters:
Address (DB)
4.3
6.0
8.0
2.
Call the SFB. The job is processed immediately. JOB_DONE only applies to SFB
run with the result FALSE. JOB_ERR = TRUE if an error occurred. Details on the
error cause are indicated at JOB_STAT.
Address (DB)
22.0
22.1
24.0
3.
A new job may be started with JOB_DONE = TRUE.
Default
Comment
FALSE
Initiates the job (edges 0-1) *
0
Job ID:
00h Job without function
01h Writes the count value
02h Writes the load value
04h Writes the comparison value
08h Writes the hysteresis
10h Writes the pulse duration
20h Writes the end value
82h Reads the load value
84h Reads the comparison value
88h Reads the hysteresis
90h Reads the pulse duration
A0h Reads the end value
0
Value for write jobs
Default
Comment
TRUE
New job can be started
FALSE
Job error
0000h
Job error ID
0000h No error
0121h Comparison value too low
0122h Comparison value too high
0131h Hysteresis too low
0132h Hysteresis too high
0141h Pulse duration too low
0142h Pulse duration too high
0151h Load value too low
0152h Load value too high
0161h Count value too low
0162h Count value too high
01FFh Invalid job ID
HB300 | CPU | 013-CCF0R00 | en | 16-40
VIPA System SLIO

Advertisement

Table of Contents
loading

This manual is also suitable for:

013-ccf0r00

Table of Contents