Fast Introduction; Hardware Configuration - Cpu - YASKAWA CPU 013C Manual

For vipa system slio
Table of Contents

Advertisement

VIPA System SLIO

8.2 Fast introduction

Overview
Steps of configuration

8.3 Hardware configuration - CPU

Precondition
HB300 | CPU | 013-CCF0R00 | en | 16-40
When disabled, the PROFIBUS interface operates as a server for communication serv-
ices with the following characteristics:
n
The PROFIBUS interface gets an "passive" PROFIBUS node, this means it is not
involved in the token rotation.
n
Via this interface you have PG/OP functions (programming, status request, control,
test).
n
The speed of the PG/OP functions is limited.
n
Bus rotation time is not influenced.
n
S7 routing is not possible.
The PROFIBUS DP slave is to be configured in the hardware configurator from Siemens.
Here the configuration happens by the sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
ment storage media - VSD, VSC' on page 83
For the configuration of the PROFIBUS DP master please follow the following approach:
n
Enable bus functionality via VSC
n
Hardware configuration - CPU
n
Deployment as DP master or DP slave
With activating the bus function 'PROFIBUS DP master' by means of the VSC,
the bus function 'PROFIBUS DP slave' is also unlocked.
n
Transfer of the complete project to CPU
With the Siemens SIMATIC Manager, the CPU 013-CCF0R00 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
The integrated PROFIBUS DP master (X3) is to be configured and con-
nected via the sub module X1 (MPI/DP).
The configuration of the CPU takes place at the Siemens 'hardware configurator' . The
hardware configurator is part of the Siemens SIMATIC Manager. It serves for project engi-
neering. Please use for configuration the Siemens SIMATIC Manager V 5.5 SP2 and up.
The modules, which may be configured here are listed in the hardware catalog. If neces-
sary you have to update the hardware catalog with 'Options è Update Catalog'.
For project engineering a thorough knowledge of the Siemens SIMATIC
Manager and the Siemens hardware configurator is required!
Option: PROFIBUS communication
Hardware configuration - CPU
Ä Chapter 4.15 'Deploy-
187