Deployment CPU M13-CCF0000

Hardware configuration - CPU

Max. number of pluggable
modules
Define addresses by hard-
ware configuration
Automatic addressing
4.4 Hardware configuration - CPU
Precondition
58
1
I/O area: 0 ... 127 (default)
2
I/O area max.: 2047
3
Process image of the inputs (PII): 0 ... 127
4
Process image of the inputs (PII) max.: 2047
5
Process image of the outputs (PIQ): 0 ... 127
6
Process image of the outputs (PIQ) max.: 2047
Up to 8 periphery modules can be connected to the CPU.
You may access the modules with read res. write accesses to the peripheral bytes or the
process image. To define addresses a hardware configuration may be used. For this,
click on the properties of the according module and set the wanted address.
If you do not like to use a hardware configuration, an automatic addressing is established.
Here the address assignment follows the following specifications:
n
Starting with slot 1, the central plugged modules are assigned with ascending logical
addresses.
n
The length of the memory area corresponds to the size of the process data of the
according module. Information about the sizes of the process data can be found in
the according manual of the module.
The memory areas of the modules are assigned without gaps separately for input and
n
output area.
n
Digital modules are mapped starting at address 0 and all other modules are mapped
starting from address 256.
n
As soon as the mapping of digital modules exceeds the address 256, by regarding
the order, these are mapped starting from address 256.
n
The configuration of the CPU takes place at the Siemens 'hardware configurator' .
The hardware configurator is part of the Siemens SIMATIC Manager. It serves for
project engineering.
n
Please use for configuration the Siemens SIMATIC Manager V 5.5 SP2 and up.
n
The configuration of the System MICRO CPU happens in the Siemens SIMATIC Man-
ager by means of a virtual PROFINET IO device 'VIPA MICRO PLC' . The 'VIPA
MICRO PLC' is to be installed in the hardware catalog by means of the GSDML.
For project engineering a thorough knowledge of the Siemens SIMATIC
Manager and the Siemens hardware configurator is required!