COMMISSIONING
Name
Value Range
[Analog output
Command
stop proof test]
[Analog output
< 1 – 3650 >
proof test
(days)
interval]
[Analog output
< Auto timeout off >
proof test
< 5 minutes >
timeout]
< 10 minutes >
< 20 minutes >
< 30 minutes >
[Analog output
< 0 – 4,294,967,295 >
proof test
(days)
elapsed time]
(RO)
[Safe state
< Enabled >
latching
< Disabled >
behavior]
230

All Outputs

Service Manual
954 SmartServo FlexLine
Default Value
Description
Terminates an active analog
output proof test. Upon
termination, the normal process
will resume and contact 2 will
close.
< 1825 >
The maximum time interval
permitted between analog
output proof tests. If exceed
and when an analog output safe
state is not active, the analog
output safety function status will
change to W to signal a warning
that a proof test is overdue. The
status code will remain as NO
ERROR.
< 5 minutes >
If not < Auto timeout off >, the
maximum time duration an
analog output proof test will
remain active. If exceeded the
proof test will automatically stop.
< 0 >
The elapsed time since the last
analog output proof test or since
commissioning if no analog
output proof test has been
executed.
Defined in
Behavior of a safe state when
section
7.3.13.1
the reason for activation no
"Safety Function
longer applies, to either
Status".
deactivate when Disabled, or
to remain active (latch) until
power is cycled when Enabled.
Part No.: 4417340 Revision 1