COMMISSIONING
Name
[Upper reference level]
[Tank top level]
[Motor limit switch high]
[Motor limit switch low]
[Dip Height]
[Dip interval time]
[Reference level]
[Accept reference]
80
Value Range
Service Manual
954 SmartServo FlexLine
Default Value
Explanation
<27.0>
The upper reference level is
used to compute the ullage
level.
The ullage level is defined
as:
Ullage level = Upper
reference level - innage
level..
<100.0>
The Tank top level is used
during a calibration test to
determine if the calculated
innage is still within
acceptable range.
<100.0>
The motor limit switch high
level indicates the highest
position the displacer
may reach during normal
operation.
This limit needs to be more
than 10 mm above the low
limit.
<200.0>
The motor limit switch low
level indicates the lowest
position the displacer
may reach during normal
operation.
<0.3>
Determines how high the
displacer will stay above the
Interface 1 (Product level)
during dip mode.
<60>
Determines the time in
between 2 consecutive
interface 1 dips
<-100.0>
Level used to set the innage
product level.
This command sets the
innage product level
indicated by the reference
level.
Part No.: 4417340 Revision 1