COMMISSIONING
7.3.6.8

Commissioned Entities

Operation
Alarm
Mode
Mode
Alarm Mode Remote
Control
PV Monitor
Not In Use
Fallback
N/A
Mode
106
By using the table below, make sure all entities are commissioned.
The [Commissioned] entity will display either <True> if the function is
commissioned or <False> if the function is not commissioned. To
commission the function, the entities must be set in accordance with the
table below.
Remote
Control
Parameters
Mode
[Control Board ID]
Restricted
[Control Board Instance]
[Control Function Instance]
[Time Setting]
[Control Board ID]
[Control Board Instance]
[Control Function Instance]
[Time Setting]
Not
[Time Setting]
Restricted
[Time Setting]
[Monitor Board ID]
Remote
[Monitor Board Instance]
[Monitor Function Instance]
[Time Setting]
[Monitor Board ID]
[Monitor Board Instance]
[Monitor Function Instance]
[Time Setting]
[Monitor Board ID]
Local
[Monitor Board Instance]
[Monitor Function Instance]
[Time Setting]
[Threshold]
[Hysteresis]
[Monitor Board ID]
Board Instance]
Function Instance]
[Time Setting]
[Threshold]
[Hysteresis]
N/A
N/A
N/A
N/A
Service Manual
954 SmartServo FlexLine
>=1 and =255
>=0 and <=7
>=1 and <=15
= 0
<1 or >255
<0 and >7
<1 and >15
≠ 0
= 0
≠ 0
>=1 and <=255
>=0 and <=7
>=1 and <=15
= 0
<1 or >255
<0 and >7
<1 and >15
≠ 0
>=1 and <=255
>=0 and <=7
>=1 and <=15
= 0
= value entered
= value entered
<1 or >255
[Monitor
[Monitor
<0 and >7
<1 and >15
≠ 0
= value entered
= value entered
Part No.: 4417340 Revision 1
Commissioned
<True>
<False>
<True>
<False>
<True>
<False>
<True>
<False>
<True>
<False>