Honeywell FlexLine SmartServo 954 Service Manual page 229

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Name
Value Range
[Contact 1
< 0 – 3.402823 × 10
hysteresis]
(meters)
[Contact 1
Status:
safety function
< H >, < O >, < U >, < W >
status]
Status Code:
(RO)
Defined in Section
[Contact 1
< 0 – 3.402823 × 10
safety
shutdown
counter]
(RO)
[Contact 1
Safety Function Status
safety
Code
shutdown
reason]
(RO)
[Contact 1
< 0 – 3.402823 × 10
switch count]
(RO)
[Contact 1
Command
Start proof
test]
Part No.: 4417340 Revision 1
Default Value
38
>
< 0.010 >
Status:
< H >
Status Code:
7.3.13.1
NO ERROR
38
>
< 0 >
NO ERROR
38
>
< 0 >
Service Manual
954 SmartServo FlexLine
Description
A value relative to the threshold
that will determine the point at
which deactivation of a contact 1
safe state occurs after activation
by an overfill or underfill
condition.
For an underfill, deactivation
occurs when the product level is
above (threshold + hysteresis).
For an overfill, deactivation
occurs when the product level is
below (threshold – hysteresis).
H: Healthy
O: Overfill condition
U: Underfill condition
W: Warning condition, safe state
is active, or proof test is overdue
(status code is NO ERROR)
The number of contact 1 safe
state activations that have
occurred since commissioning.
The safety function status code
identifies the reason for the last
time a contact 1 safe state
activation occurred.
The number of contact 1
closures, or transitions from safe
state to normal state, since
commissioning.
Initiates a contact 1 proof test if
an actual contact 1 safe state is
not currently active. Upon
activation, contact 1 will open to
simulate a safe state. An active
poof test will terminate if an
actual contact 1 safe state is
activated, or if the contact 1
proof test timeout value is
exceeded.
221