Relay Outputs; Instruction For Setting The Relay Outputs As No / Nc Or Supervised - Honeywell MA-1000 Installation Manual

Hide thumbs Also See for MA-1000:
Table of Contents

Advertisement

6.2.2 Relay outputs

FUNCTION
CHARACTERISTICS
Sounder Circuit
1 contact controlled by 24 Vcc / 1 A resistive
USR2
Max 1 A resistive 30 V DC, NO / NC or supervised output 0,3 A Fused, selectable through
Jumper JUSR2 (refer to basic board topography)
USR1
Max 1 A resistive 30 V DC, NO / NC or supervised output 0,3 A Fused, selectable through
Jumper JUSR1 (refer to basic board topography)
General Alarm
Max 1 A resistive 30 V DC, NO / NC or supervised output 0,3 A Fused, selectable through
Jumper JALL (refer to basic board topography)
General Fault
Max 1 A resistive 30 V DC, NO / NC or supervised output 0,3 A Fused, selectable through
Jumper JGST (refer to basic board topography)

6.2.3 Instruction for setting the relay outputs as NO / NC or supervised

M-167.1-MA1000-EN / 02.2023
The setup show is valid for the output:
JUSR1: User 1
JUSR2: User 2
JALL: Alarm
MA-1000
21