Flexconn Function Allocation - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Table 7-1
Part No.: 4417340 Revision 1
As an alternative function, the FCI-HT board also allows the connection
of up to 5 generic HART sensors operating in multi-drop digital mode or
one generic HART sensor operating in analog mode.
In the multi-drop digital mode situation, one or two of the generic HART
sensors can be
[P1 Pressure]
and Vapour pressure respectively, but no HIMS density calculation will
be available.
The HART sensors and HIMS density measurement are allocated to a
function number in the FCI-HT software. See table below.
FlexConn Function
Function 1
Function 2
Function 3
Function 4
Function 5
Function 6
Function 7
Function 8

FlexConn function allocation

Function 1 is exclusively reserved for P1 pressure, Function 2 is
exclusively reserved for P3 pressure, and Function 8 is exclusively
reserved for HIMS density calculation.
Only one of each type of HART device can be allocated to a function.
Therefore, this limits the number of HART devices of each type that can
be fitted.
Example 1
4 HART pressure devices and 1 temperature device can be connected.
P1 pressure device allocated to Function 1
P3 pressure device allocated to Function 2
one pressure device allocated to Function 5
one pressure device allocated to Function 7
the temperature device allocated to Function 4
Service Manual
954 SmartServo FlexLine
or
[P3
Pressure], providing product pressure
Device Type
[P1 Pressure]
[P3 Pressure]
[Distance]
[Temperature]
[Pressure]
[Density]
[Other]
[HIMS Density]
111