Fcm-Trl/2 Modbus Master - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Figure 7-33
172
On the TAB sheet TRL/2 Modbus Master gauges modbus address
can be set (Refer to

FCM-TRL/2 Modbus Master

NOTE: You can enter maximum 20 gauges Modbus address for
commissioning at a time. If you want to commission more gauges,
delete the first 20 modbus address on the TRL2 Modbus page after
commissioning them and add next 20 gauges address and commission
them. All the gauges will be listed on the left pane after every
commissioning.
Identification:
An 8 character long name for the FCM- TRL/2 board.
GPU instrument start address:
GPU instrument stop address:
When one FCM- TRL/2 Module is used in the SmartLink, the default
start and stop addresses (0 and 99) can be used.
When two or three FCM-TRL/2 Modules are used in the SmartLink, a
division must be made of the full range; for instance:
l 99 for the second FCM- TRL/2 Module or
0 till 29 for the first FCM- TRL/2 Module
Service Manual
954 SmartServo FlexLine
"FCM-TRL/2 Modbus Master").
Figure 7-33
Part No.: 4417340 Revision 1