COMMISSIONING
Name
[Lowest element offset]
[Sensor length]
Name
[Product immersion depth]
[Hysteresis]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
Part No.: 4417340 Revision 1

Product Temperature

The following entities must be set by Engauge or HART
SmartView for a correct functioning of the FII-VT module in an
instrument.
NOTE: Using Engauge, following entities are set within the Engauge
Product temperature tab.
Explanation
The distance from tank zero
till the lowest element
position in the temperature
probe
The distance from the
Pt100 position till the
highest element position
The following entities can be set by Engauge or HART SmartView for a
correct functioning of the FII-VT module in an instrument.
Check each entity for its correctness.
Explanation
The minimum required
distance of the product
level above an element
before it is taken into
account in the average
product temperature
calculation
The distance for a
hysteresis mechanism
around the switching point
of the elements that are
taken into account in the
calculation
4 thresholds for activating a
related alarm status in the
Primary Value
Service Manual
954 SmartServo FlexLine
Value Range
floating point number:
<-x.x .. +x.x>
floating point number:
<-x.x .. +x.x>
Value Range
floating point number:
<-x.x .. +x.x>
floating point number:
<-x.x .. +x.x>
floating point number:
<-x.x .. +x.x>
Default
<80.0>
<80.0>
Default
<0.5>
<0.1>
<+1.0E22>
123