Honeywell FlexLine SmartServo 954 Service Manual page 140

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Name
[Gas immersion depth]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
[Alarm test enable]
[Alarm test]
[Function identification]
132
Vapour Temperature
NOTE: Using Engauge, following entities are set within the Engauge
Vapour temperature tab.
Some Vapour temperature settings are shared with Product
temperature settings.
The following entities can be set by Engauge or HART SmartView for a
correct functioning of the FII-VT module in an instrument.
Check each entity for its correctness.
Explanation
The minimum required
distance below an element
before it is taken into
account in the average
Vapour temperature
calculation
4 thresholds for activating a
related alarm status in the
Primary Value
Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
Activates and selects at the
same time the Alarm test (if
enabled with the
enable]
listed before, and the
4 alarm thresholds are
properly set).
The current module's
function name. This
function is visible on the
HART SmartView
display.
Service Manual
954 SmartServo FlexLine
Value Range
floating point number:
<-x.x .. +x.x>
floating point numbers:
<-x.x .. +x.x>
<enable>
<disable>
[No Alarm]
[High High
[Alarm test
alarm] [High
Alarm]
[Low Alarm]
[Low Low alarm]
13 characters
Default
<0.5>
<+1.0E22>
<disable>
<No Alarm>
<Vapour temp.>
Part No.: 4417340 Revision 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents