Honeywell FlexLine SmartServo 954 Service Manual page 161

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Part No.: 4417340 Revision 1
NOTE: Commands used in the following calibration procedure can be
executed either by using the CAN tool, the HART SmartView, or
Engauge.
Calibrate the analog output of the HCI-HAO as follows:
Connect loop resistor at connector CN2
Power up HCI-HAO board
Give command [Enter Calibration Mode]
Give command [Calibrate Analog Output at 4mA]
Measure actual output current through the loop resistor, using a
current meter
Enter this value in the
Give command [Calibrate Analog Output at 18mA]
Measure actual output current through the loop resistor, using a
current meter
Enter this value in the
[Exit Calibration
Give command
These calibration data are used to calculate the analog output current
for the Primary Value (PV).
Until calibration has been carried out, the Health status of the PV and
the analog output function will be:
Status
<BAD>
<STATUS_CATEGORY_BAD_GENERAL_CALIBRATION_FAIL>
Status Category
<CALIBRATION_SET_POINTS_NOT_CALIBRATED>
Status Code
Service Manual
954 SmartServo FlexLine
[Analog Output at 4mA]
entity
[Analog Output at 18mA]
Mode], to exit the calibration mode
entity
153