COMMISSIONING

7.3.10.3 Before You Begin Migration

7.3.10.3.1 Device Mapping

Rex
AI
HART
Option 1
2
0
Option 2
1
1
Part No.: 4417340 Revision 1
NOTE: Ensure that the following devices/network/Hosts should be
physically protected in a controlled area:
Gauge and the SmartLink devices
Networks in which the Gauge and the SmartLink nodes operate
Hosts that connect to the Gauge and the SmartLink nodes
operate

Before mapping the device:

®
Enraf
FCU checklist: Note the FCU unit ID and FCU modbus
address. Cross verify the data base about these entries.
Communication overview: Note the field port that FlexLine will
replace and its corresponding group port, if Rex is connected to
®
Enraf
FCU. Confirm with saved database.
RTG general information: Note the RTG unit ID and modbus
address This is required for configuring TRL/2.
Data Acquisition Unit: Note the unit ID and modbus address
(Required for configuring TRL/2).
Operator Software: Verify the data base, the unit ID and
Modbus, address of Rex/RTG, Data Acquisition Unit and Enraf
FCU and the number of field ports to which Rex/RTG is attached
and the number of group ports to which the system with
Rosemount Tankmaster is attached. Also note whether the other
group port is connected or free.
The following table describes the possible combination of cards:
AO
Relay Temp
0
1 or 2
6 or 14 Option1: HRT-1 (AI1 & AI2 as HART input), FII-
0
1 or 2
6 or 14 Option1: HRT-1(HART, AI as HART & Temp),
Service Manual
954 SmartServo FlexLine
Possible combinations of cards in
FlexLine Gauge
DO (Relay) and FII-RTD/ HRT-1. (3 cards).
Option2: HRT-1 (AI1), HART-2 (AI2), FII-DO
(Relay) and FII-RTD/ HRT-3. (4 cards).
SMV card (Display) NOT possible for option 2.
FII-DO (Relay) - (2 cards) Option2: HRT-
1(HART & Temp), HART-2 (AI), FII-DO (Relay)
- (3 cards)
Option3: HRT-1(HART), HART-2 (AI), FII- DO
(Relay) & FII-RTD - (4 cards)
SMV card (Display) NOT possible for option 3.
®
161