COMMISSIONING
7.3.9.6
Commissioning
Name
[PV Link board ID]
[PV Link board instance]
[PV Link function instance]
[PV Link Sensor Value]*
[HART PV unit code]
[HART Upper Transducer
Limit]
[HART Lower
Transducer Limit]
[Polling Address]
[Transducer Serial
Number]
[Upper Range Value]
[Analog Output at 4mA]
[Analog Output at 18
mA]
[Lower Range Value]
[Analog Burnout Value]
*) Default values for entities marked in
the above table could be considered as proper
Part No.: 4417340 Revision 1
The following entities must be set by Engauge or HART
SmartView for a correct functioning of the HCI-HAO module in an
instrument.
Explanation
Board ID of Other FlexConn
to be linked as PV to HCI-
HAO
Board Instance of the linked
PV board
Function Instance of the
linked PV board
Primary or secondary
variable of linked card can
be assigned to this
Unit code for linked PV
Upper transducer limit for
connected sensor of linked
PV board
Lower transducer limit for
connected sensor of linked
PV board
Polling address of the
device, which is used for
poll-based addressing
Transducer serial number
of connected sensor of
linked PV board
Upper range value for PV.
This value is used to
calculate the analog output
current.
Calibration reading when
[Calibrate at 4 mA]
command
is given
Calibration reading when
[Calibrate at 18 mA]
command
is given
Lower range value for PV.
This value is used to
calculate the analog output
current.
Analog burnout value in
case of malfunctioning
device
GREEN
Service Manual
954 SmartServo FlexLine
Function
Default
Part
Value
<0>
Board
<0>
<0>
<PV_LINK>
<UNIT_CODE_
Function 1 Communication
UNKNOWN>
<0>
<0>
<0>
<123>
<0>
Function 2 Sensor
<0>
<0>
<0>
<3.6mA>
in
Function
Board Specific
(HART
communication)
(Analog Output)
155