COMMISSIONING
7.3.3.2

Commissioning the HCI-BPM

Name
[Baudrate]
[BPM sensitivity]
[Identification]
[GPU instrument address]
[FlexConn instrument address]
[Level units]
[Temperature units]
Part No.: 4417340 Revision 1
The HCI-BPM module supports the following two protocols
The Enraf GPU protocol with its records and items (limited);
The Enraf FlexConn protocol with its entities.
The module can communicate with the following:
880 CIU prime
858 CIU
780 SmartLink
For a correct functioning of the HCI-BPM module in an instrument
(gauge), the following entities can be set by using either Engauge or
HART SmartView.
By using the following table, check each entity for correctness.
Value Range
<1200>
<2400>
<4800>
<1..8>
8 characters for example,
<TANK1234>
<0..99>
<0..1899>
<Meters>
<Inches>
<Feet>
<Fractions>
<Celsius>
<Fahrenheit>
Service Manual
954 SmartServo FlexLine
Default Value
Explanation
<1200>
Communication speed
<8>
The sensitivity of the
receiver circuit.
1 = weakest
8 = strongest
<-------->
Name of a tank or
instrument.
<0>
The address of this
instrument for GPU
messages.
Note: Each instrument must
have a unique GPU
address.
<0>
The address of this
instrument for FlexConn
messages.
Note: Each instrument must
have a unique FlexConn
address.
<Meters>
The unit in which level-
related GPU records and
items are displayed.
<Celsius>
The unit in which
temperature-related GPU
records and items are
displayed.
59