COMMISSIONING
7.3.3.2
Commissioning the HCI-BPM
Name
[Baudrate]
[BPM sensitivity]
[Identification]
[GPU instrument address]
[FlexConn instrument address]
[Level units]
[Temperature units]
Part No.: 4417340 Revision 1
The HCI-BPM module supports the following two protocols
•
The Enraf GPU protocol with its records and items (limited);
•
The Enraf FlexConn protocol with its entities.
The module can communicate with the following:
•
880 CIU prime
•
858 CIU
•
780 SmartLink
For a correct functioning of the HCI-BPM module in an instrument
(gauge), the following entities can be set by using either Engauge or
HART SmartView.
☛
By using the following table, check each entity for correctness.
Value Range
<1200>
<2400>
<4800>
<1..8>
8 characters for example,
<TANK1234>
<0..99>
<0..1899>
<Meters>
<Inches>
<Feet>
<Fractions>
<Celsius>
<Fahrenheit>
Service Manual
954 SmartServo FlexLine
Default Value
Explanation
<1200>
Communication speed
<8>
The sensitivity of the
receiver circuit.
1 = weakest
8 = strongest
<-------->
Name of a tank or
instrument.
<0>
The address of this
instrument for GPU
messages.
Note: Each instrument must
have a unique GPU
address.
<0>
The address of this
instrument for FlexConn
messages.
Note: Each instrument must
have a unique FlexConn
address.
<Meters>
The unit in which level-
related GPU records and
items are displayed.
<Celsius>
The unit in which
temperature-related GPU
records and items are
displayed.
59