COMMISSIONING
Name
[Pressure units]
[Density units]
[Decimal separator]
[Level type]
[Password]
[Function identification]
60
Value Range
<pascal>
<kilo pascal>
<psi small>
(2 digits before
separator)
<psi large>
(3 digits before
separator)
<kilogram m3>
<degrees API>
<pounds ft3>
<point>
<comma>
<innage>
<ullage>
<......>
6 characters
<......>
13 characters
After having checked/set all before listed entities, make sure you
check the following:
The [Board Commissioned] and the [BPM slave
Commissioned] entities are <True>.
The [Board Health] and the [BPM slave Health] entities are
<GOOD>.
Service Manual
954 SmartServo FlexLine
Default Value
Explanation
<pascal>
The unit in which pressure-
related GPU records and
items are displayed.
<kilogram m3>
The unit in which density-
related GPU records and
items are displayed.
<point>
The decimal separator in
which GPU-related records
and items are displayed.
<innage>
The level-related GPU
records and items can be
shown as an innage or
ullage.
Note:
<ENRAF2>
Password for entering the
protected level.
Note: Some settings reside
under the protected level.
<BPM-slave>
The name of the current
function of this module.
This name is visible on the
HART SmartView display.
Part No.: 4417340 Revision 1
Innage is the level of the
product measured from
the bottom.
Ullage is the level of
free space from the roof
till the product.