Status Entities On Hart Smartview - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

SYSTEM ARCHITECTURE

Status Entities on HART SmartView

26
Status Category
over range
under range
no data available
un-initialized
killed
Select sub-menu "commissioning" from the main menu to view the
survey results of all FlexConn modules present in the 954 SmartServo
FlexLine system.
Each module is followed by an indication for the "Health" and the
"Commissioned" status respectively. In case of an unreliable or fault
situation, the "Information" column displays an information code in
addition. This information code reveals the specific reason about the
current status.
This diagnostic is available for each individual FlexConn module. See
example below.
FII-DO
The "Health" indication is as follows:
"G" = Good
"U" = Uncertain
"B" = Bad
The "Commissioned" indication is as follows:
"Y" = the most important entities are set correctly
"N" = the most important entities are not set correctly
Starting from the "commissioned" menu and selecting the specific
FlexConn module, the above diagnostics is repeated for each
module function. See example below.
FII-DO:>
board
Relay 1
Relay 2
Relay 3
Relay 4
Service Manual
954 SmartServo FlexLine
Display Text
over range
under range
no data
no init
killed
H C I
G N
H C I
G N
G Y
U Y nnn
B Y