COMMISSIONING
7.3.8.4.3
Name
[Lowest element offset]
[Number of elements]
[Element type]
[Measurement type]
142
Commissioning Parameters for MRT Temperature Calculations
NOTE: Make sure the RTD/MPT jumper is set to MRT (= MPT
position).
☛
The following entities must be set by Engauge or HART SmartView
for a correct functioning of the FII-RTD module in an instrument. The
default values are available after initialization of the non-volatile
memory.
Explanation
The distance from tank zero
till the bottom of the probe
The number of elements
used
The type (material) of the
used RTDs
Selects RTDs, MPT, or
MRT.
Service Manual
954 SmartServo FlexLine
Value Range
floating point number:
<-x.x .. +x.x>
<1..6>
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + beacon + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
Part No.: 4417340 Revision 1
Default
<80.0>
<0>
<No type>
<No type>