Calibration Of The Hci-Hao - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
7.3.9.4

Calibration of the HCI-HAO

152
Multi-drop mode supported to connect more than one
HART- compatible device on HART bus. For operating the
device in Multi- Drop mode, user needs to select the polling
address to a non-zero value. Making the polling address to a
non-zero value makes the output current mode to
Fixed_4_20_MA
automatically make the output current mode to Fixed_4_20_MA.
All the HART-compatible devices connected over the HART
bus must have different polling addresses. Multi-drop mode is
supported only in Passive mode of loop configuration. When
the output current mode is set to Standard_4_20_MA, the polling
address of the device must be made zero.
When the device is not in multi-drop mode
mode selected) then the output current follows the changes in
linked PV value.
Scanning of each linked available PV, SV, TV and QV on the
CAN- bus with frequency of 1 Hz. That means all the available
linked variables are scanned every 1 second.
The analog output is refreshed every 1 second, even if there
is no change in the scanned variables. So, the watchdog for
analog output is automatically implemented. If the output is not
refreshed within 45 seconds then a watchdog to analog output
is generated and the output is forced to 0 mA.
During startup, the analog output of the HCI-HAO module is kept
low (< 0.5 mA). This value will be there till initialization takes
place. Once the normal operation starts the output will follow
the linked PV depending upon the output mode setting.
Manual overwrite mechanism. This is a standard FlexConn
func-tionality. Separate configuration and command entities
are defined for this. See
A calibration provision is given, which is used to accurately map the
analog output between 4 -20 mA using the two range values entered for
Primary Variable.
Following table lists all entities required for calibration.
Entity
[Analog Output at 4 mA]
[Analog Output at 18 mA]
[Calibrate at 4 mA]
[Calibrate at 18 mA]
[Enter Calibration Mode]
[Exit Calibration Mode]
Service Manual
954 SmartServo FlexLine
(4 mA fixed). Non-zero polling address will
7.3.9.5
- Board Commissioning.
Data Type
Float
Float
Undefined
Undefined
Undefined
Undefined
(STANDARD_4_20_MA
Type
non-volatile R/W
non-volatile R/W
command
command
command
command
Part No.: 4417340 Revision 1