Commissioning Parameters For Mpt Temperature Calculations - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
7.3.8.4.2
Name
[Lowest element offset]
[Number of elements]
[Element type]
[Measurement type]
[MPT sensor length]
Part No.: 4417340 Revision 1

Commissioning Parameters for MPT Temperature Calculations

NOTE: Make sure the RTD/MPT jumper is set to MPT.
The following entities must be set set by Engauge or HART
SmartView for a correct functioning of the FII-RTD module in an
instrument. The default values are available after initialization of the
non-volatile memory.
Explanation
The distance from tank zero
till the bottom of the probe
The number of elements
used
The type (material) of the
used RTDs
Selects RTDs, MPT, or
MRT.
The length of the MPT
probe
Service Manual
954 SmartServo FlexLine
Value Range
floating point number:
<-x.x .. +x.x>
<1..6>
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + beacon + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
floating point number:
<-x.x .. +x.x>
Default
<80.0>
<0>
<No type>
<No type>
<80.0>
141