Roof Immersion (Ric) - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING

7.3.4.17 Roof Immersion (RIC)

Name
Value Range
[HART level addr
11,12,13]
[Status]
[Compensation
factor]
[Probes scan
<0..255>
board id]
[Probes scan
<0..7>
board instance]
[Method]
<Geometrical>
<Roof weighing>
[Total surface
area product]
Part No.: 4417340 Revision 1
Default Value
Explanation
Shows the level measured by the HART
probe at HART address 11,12,13, takelcd
n into account the configured units.
Shows the status of the calculated RIC
compensation factor, which can be:
No error
RIC configuration parameters not
commissioned
Product level below RIC minimum level
Error getting HART dynamic variables entity
device address 11
Error getting HART dynamic variables entity
device address 12
Error getting HART dynamic variables entity
device address 13
Wrong HART units device address 11
Wrong HART units device address 12
Wrong HART units device address 13
Bad HART status device address 11
Bad HART status device address 12
Bad HART status device address 13
Shows the calculated compensation offset
due to the roof immersion. This will be
applied to the L-record. Normally this will be
a negative number.
<0>
Determines the board id where the probes
are connected. This can be:
6 : FCI-HT
7 : FII-VT
23: FCI-HRT
<0>
Determines the board instance of the above
mentioned board.
<Geometrical>
Two possible methods for doing the
calculations. They are recommended by the
Polish Weight and Measures Institute called
the G.U.M.
<0.0>
Determines the total surface area of the
product in the tank.
Service Manual
954 SmartServo FlexLine
95