2. Tighten the four PEM panel fasteners in both the back and the front of the fan
tray.
3. Connect the sequencer serial cable.
4. Connect the power cord.
5. Verify that all fans are functioning.
6. Close the back door.
10.5

Adding a Cabinet in the Field

Use the following procedure to add a second cabinet to a single Sun StorEdge 3900
and 6900 series system.
Note – The names of the Sun StorEdge T3+ arrays in the second cabinet are shown
in
FIGURE 3-1

To Add a Cabinet in the Field

1. Set up the second cabinet and connect the cables as described in the Sun StorEdge
3900 and 6900 Series 1.1 Installation Guide.
2. Locate the media access control (MAC) address of the Sun StorEdge T3+ array(s).
The MAC address is located on the inside of the front cover of the device.
3. Log in to the Storage Service Processor.
Refer to the procedures in Section 12.2, "Connecting to the Storage Service
Processor" on page 12-2 for instructions.
and
.
FIGURE 3-2
Chapter 10 Servicing the Expansion Cabinet
10-9