Advertisement

5.14.6 Frequency Output Range Setting

When the frequency output is used, the frequency at 0% and 100% can be specified for the span
of the process value. The frequency output range can be set by specifying the frequency.
Set the output frequency for the span of the process value which is assigned to PV in Subsection
5.1.2.
The setting can be configured with the following parameters.
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
MTB
110
MTB
111

5.14.7 Status Output Function Setting

When the status output is used, the device status can be output as a contact point.
The setting can be configured with the following parameter.
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
MTB
112
From the table below, select the status output function.
Selection
Display
No function
Alarm output
Warning output
Total limit 1
Total limit 2
Device setup ► Detailed setup ► Pulse/Status out ► PO1/SO1 ► (see below)
Device Configuration ► MTB ► Device Configuration ► Maintenance ► Pulse/Status Out
► (see below)
Parameter
Display
Frequency at 0%
Frequency 1 at 0%
Frequency at 100%
Frequency 1 at 100%
Device setup ► Detailed setup ► Pulse/Status out ► PO1/SO1 ► (see below)
Device Configuration ► MTB ► Device Configuration ► Maintenance ► Pulse/Status Out
► (see below)
Parameter
Display
SO1 function
SO1 Function
F
OUNDATION
Fieldbus
The status output is not available because the status output function is
No function
not enabled.
Alarm output
The status output is activated when the specific alarm occurs.
Warning output
The status output is activated when the specific warning occurs.
The status output is activated while the totalized value of totalizer 1
Total limit 1
is out of the set target value. For details about the totalization switch
function, refer to Subsection 5.2.3.
The status output is activated while the totalized value of totalizer 2
Total limit 2
is out of the set target value. For details about the totalization switch
function, refer to Subsection 5.2.3.
<5. Functions>
F
Fieldbus
OUNDATION
F
Fieldbus
OUNDATION
Description
168
Description
Specifies the output frequency
when the process value is 0%.
Specifies the output frequency
when the process value is
100%.
Description
Specifies the status output
function.