YOKOGAWA Admag TI Series User Manual page 131

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Block
Relative
Name
Index
DTB
28
Threshold level 4
DTB
29
Result ► Status
DTB
30
Check cycle
*1:
From the table below, select the use of the electrode adhesion detection function.
Selection
F
OUNDATION
Display
Fieldbus
Disable
Disable
Enable
Enable
NOTE
If the electrode adhesion detecting function is not used, the electrode resistance value and level
are cleared.
NOTE
Before using the electrode adhesion detecting function, be sure to make sure that the sensor is in
the full pipe state. If the sensor is in the empty pipe state, the function to detect adhesion may not
run normally.
NOTE
The electrode adhesion detecting function is restricted by the conductivity of fluid. The
recommended conductivities are as follows.
Meter size
2.5 to 10 mm
15 to 400 mm (0.5 to 16 in.)
500 mm
NOTE
If the data update cycle for the adhesion detection is shortened, the error of the electrode
resistance value increases. Do not change the default value unless especially specified.
Parameter
Display
F
OUNDATION
Adhesion Level4
Adhesion Status
Adhesion Check Cycle
Does not use the electrode adhesion detecting function.
Uses the electrode adhesion detecting function.
Conductivity
30 μS/cm or larger
10 μS/cm or larger
20 μS/cm or larger
<5. Functions>
Description
Fieldbus
Specifies the value to judge
level 4.
Displays the electrode
adhesion detection level.
Specifies the data update
cycle for electrode adhesion
detection.
Description
130
IM 01E21A02-03EN