Totalization Function; Totalized Value And Unit Setting; Totalized Value Display And Totalization Counter Function - YOKOGAWA Admag TI Series User Manual

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

5.2

Totalization Function

5.2.1

Totalized Value and Unit Setting

This product has two totalizers for TB in addition to IT FB. A process value which can be set for
the totalizer on the TB side is a volumetric flow rate, mass flow rate, and calorie.
When Totalizer 1 and Totalizer 2 are selected as the channel of the AI function block, a unit can
be set with following steps in 5.1.4 Engineering Unit Setting.
The set unit can be displayed with the following parameters.
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
48
STB
50
5.2.2
Totalized Value Display and Totalization Counter
Function
The totalization result can be displayed with a totalized value or a totalized value which is scaled
with the conversion factor (totalized count value). When the totalized value is scaled with the
conversion factor, a specific flow rate is totalized in 1-count increments, which can be used as a
totalizer counter.
The totalized value can be displayed and configured with the following parameters.
Displaying totalized value
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
47
STB
49
Device setup ► Detailed setup ► Totalizer ► (see below)
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Parameter
Display
Totalizer 1 ► Unit
Total 1 Unit
Totalizer 2 ► Unit
Total 2 Unit
Device setup ► Process variables ► Totalizer ► (see below)
Process Variables ► STB ► Process Variables ► Dynamic Variables ► Device Variables
► (see below)
Display
Total 1 Value ► Total 1 Value.
-
Status
Totalizer 1
Total 1 Value ► Total 1 Value.Value
Total 2 Value ► Total 2 Value.
-
Status
Totalizer 2
Total 2 Value ► Total 2 Value.Value
F
Fieldbus
OUNDATION
Parameter
F
Fieldbus
OUNDATION
<5. Functions>
Description
Displays the unit of totalizer 1.
Displays the unit of totalizer 2.
Description
Status of totalizer 1.
Displays the value of
totalizer 1.
Status of totalizer 2.
Displays the value of
totalizer 2.
IM 01E21A02-03EN
66

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Admag ti axgAdmag ti axw

Table of Contents