Advertisement

5.2.4

Operation of Totalizer Function at Alarm Occurrence

The operation of the totalizer can be specified when an alarm that affects the totalization function
occurs.
The setting can be configured with the following parameters.
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
69
STB
78
From the table below, select the operation of the totalization function.
Selection
Display
Measured value
Stop
Last valid
5.2.5

Start/Stop Setting for Totalization Function

The start/stop operation of the totalization function can be set.
The setting can be configured with the following parameters.
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
71
STB
80
NOTE
The totalization function is set to "Stop" at shipment from the manufacturing factory. To start the
totalization function, be sure to set the function to "Start".
Device setup ► Detailed setup ► Totalizer ► (see below)
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Display
Totalizer 1 ► Failure opts
Totalizer 2 ► Failure opts
F
OUNDATION
Fieldbus
Continues the totalization function with an instantaneous value at that
Measured value
time even while an alarm is occurring.
Displays the totalized value up to that point by immediately stopping the
Stop
totalizer if an alarm occurs.
Continues the totalization function with the last instantaneous value
Last valid
right before an alarm occurs (monotonical increasing).
Device setup ► Detailed setup ► Totalizer ► (see below)
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Parameter
Display
Totalizer 1 ► Start/Stop Totalizer1 ► Total 1 Execution
Totalizer 2 ► Start/Stop Totalizer2 ► Total 2 Execution
Parameter
F
Fieldbus
OUNDATION
Totalizer1 ► Total 1 Failure
Opts
Totalizer2 ► Total 2 Failure
Opts
Description
F
Fieldbus
OUNDATION
<5. Functions>
Description
Specifies the totalizer 1
operation to be performed
when an alarm occurs.
Specifies the totalizer 2
operation to be performed
when an alarm occurs.
Description
Specifies Start/Stop to the
totalization function of totalizer
1.
Specifies Start/Stop to the
totalization function of totalizer
2.