Page 1
User’s ADMAG TI Series Manual AXG/AXW Magnetic Flowmeter AXG/AXW Magnetic Flowmeter Safety Manual IM 01E21A21-02EN IM 01E21A21-02EN 2nd Edition...
For the items which are not covered in this manual, read the applicable user’s manuals and general specifications as listed in Table 1.1. These documents can be downloaded from the website of YOKOGAWA. To ensure correct use of the product, read these manuals thoroughly and fully understand how to operate the product before maintaining it.
Page 4
Configurations other than the above (e.g., Remote Sensor and AXFA11G Remote Transmitter) cannot be used for safety instrumentation systems. The certificate can be downloaded from the website below. Website address : https://www.yokogawa.com/library/ NOTE When describing the model name like AXG in this manual, “”means any of the following.
Page 5
Take special note that if you handle the product in a manner that violated these instructions, the protection functionality of the product may be damaged or impaired. In such cases, YOKOGAWA shall not be liable for any indirect or consequential loss incurred by either using or not being able to use the product.
<1. INTRODUCTION> Safety Instrumented Systems Installation WARNING The contents are cited from exida.com safety manual on this product specifically observed for its safety purpose. When using this product for Safety Instrumented System (SIS) application, the instructions and procedures on this chapter must be strictly followed in order to preserve this product for that safety level. Scope and Purpose This chapter provides an overview of the user responsibilities for installation and operation of this product in order to maintain the designed safety level for SIS applications.
<2. Safety Instrumented Systems Installation> 2.2.4 Setup Set the ranges and units via the BRAIN or HART configuration tool. After configuration, make sure that they are set correctly. The calibration of this product must be carried out after parameters are set. For its parameter settings, read Chapter 4 and Chapter 5 in the user’s manual of applicable communication type as listed in Table 1.1.
Proof test results are required to be documented. And this documentation should be a part of the plant safety management system. Failures that are detected should be reported to YOKOGAWA. The personnel carrying out the proof test of products should be trained in SIS operations including bypass procedures, maintenance of this product, and company management of change procedures.
Page 9
<2. Safety Instrumented Systems Installation> Example of generating an alarm current output; (In case of “66:Dens cfg ERR” for BRAIN (“Density configuration error” for HART)); (1) Set parameters through BRAIN or HART communication protocol in order to generate an alarm at “Analog Output 1”...
2.2.9 Firmware Update The user will not be required to carry out any firmware updates. When its updates work is required, it must be carried out at YOKOGAWA. 2.2.10 Reliability Data Refer to the FMEDA report (YEC 16/03-009 R002 V2R4) for failure rates and failure modes. The FMEDA Report can be downloaded from the website below.
<2. Safety Instrumented Systems Installation> Definitions and Abbreviations 2.3.1 Definitions ● Safety Definition Contents Safety Freedom from unacceptable risk of harm. Functional Safety The ability of a system to carry out the actions necessary to achieve or to maintain a defined safe state for the equipment/machinery/plant/apparatus under control of the system.
<Revision Information> Revision Information Title : ADMAG TI Series AXG/AXW Magnetic Flowmeter Safety Manual Manual No. : IM 01E21A21-02EN Edition Date Page Revised Item June 2017 — New publication Feb. 2022 Revise Table 1.1 Document title and No.