Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Index
Relative
Index
DI1
DI2
DI3
21
6021 6121 6221 ACK_OPTION 0xFFFF
22
6022 6122 6222 DISC_PRI
23
6023 6123 6223 DISC_LIM
24
6024 6124 6224 DISC_ALM
Parameter
Default Value
Name
0
0
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0(State 0)
<6. Parameter Lists>
Write
Description
Mode
Sets operation
to acknowledge
(acknowledgment for
the alarm) of various
alarms. By setting a bit
to the alarm, the device
AUTO
operates for the alarm as if
it is acknowledged without
the acknowledgment.
Bit assignment complies
with the Communication
standard specifications.
AUTO
Specifies the alarm priority.
Indicates the input
status for discrete alarm.
Meanwhile, to activate an
alarm on communication,
it is necessary to specify
the priority for alarm
activation in advance. To
activate an alarm, set 3
AUTO
or more. By sending with
priority information being
added in a communication
frame when the alarm is
activated, for example, the
alarm is used to apply a
filter to ignore values below
the specified priority on the
host side.
AUTO
-
Indicates the status related
-
to discrete alarm.
-
-
216