Span Setting - YOKOGAWA Admag TI Series User Manual

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
67
STB
76
NOTE
If there is inconsistency between the process value selected in the AI FB channel and the unit set
with XD scale Units index, Bit1 in Block Error of the AI function block is set on.
Example:
AI Channel: 2 (volumetric flow rate), XD scale Units index (Transducer Scale.Units Index): 1328
(t/h)
5.1.5

Span Setting

The flow velocity, volumetric flow rate, mass flow rate, and calorie can be set from Sensor TB.
However, the unit of the span is the unit set in Subsection 5.1.4.
If the flow rate unit is changed, the span value is converted in conjunction with the changed unit.
The setting can be configured with the following parameters.
Flow velocity, volumetric flow rate, mass flow rate, calorie
Menu path
Display
F
OUNDATION
Fieldbus
Block
Relative
Name
Index
STB
62
STB
63
STB
64
STB
65
Device setup ► Detailed setup ► Totalizer ► (see below)
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Parameter
Display
Totalizer 1 ► Unit
Totalizer 1 ► Total 1 Lowcut
Totalizer 2 ► Unit
Totalizer 2 ► Total 2 Lowcut
Device setup ► Detailed setup ► Pro var ► (see below)
Device Configuration ► STB ► Device Configuration ► Configuration ► Process
Variables ► (see below)
Parameter
Display
Velocity ► Span
Velocity ► Velocity Span
Volume Flow ► Volume Flow
Volume ► Span
Span
Mass ► Span
Mass Flow ► Mass Flow Span
Calorie ► Span
Calorie ► Calorific Span
<5. Functions>
F
Fieldbus
OUNDATION
F
Fieldbus
OUNDATION
Description
Displays the unit of totalizer 1.
Displays the unit of totalizer 2.
Description
Specifies the span of the flow
velocity.
Specifies the span of
volumetric flow rate.
Specifies the span of the mass
flow rate.
Specifies the span of the
calorie.
(Only available for AXG, not for
AXW).
IM 01E21A02-03EN
56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Admag ti axgAdmag ti axw