NE
107
Display
N
375:AI3 Lo Alarm
N
376:AI4 HH Alarm
N
377:AI4 LL Alarm
N
378:AI4 Hi Alarm
N
379:AI4 Lo Alarm
N
392:PID HH Alarm
N
393:PID LL Alarm
N
394:PID Hi Alarm
N
395:PID Lo Alarm
Setting alarm
The device works normally, but the parameter setting error occurs.
Parameter setting is needed.
NE
107
Display
S
060:Span cfg ERR
S
066:Density cfg ERR
S
067:Pls 1 cfg ERR
Error Message
F
OUNDATION
Fieldbus
AI3 Low Alarm
AI4 High High Alarm
AI4 Low Low Alarm
AI4 High Alarm
AI4 Low Alarm
PID High High Alarm
PID Low Low Alarm
PID High Alarm
PID Low Alarm
Error Message
F
OUNDATION
Fieldbus
Span configuration
error
Density
configuration error
Pulse output 1
configuration error
<5. Functions>
Error Description
Check AI3 Output
Low alarm occurred in
Value and settings of
the AI3 block.
AI3 Lo Lim and AI3 Lo
Pri.
Check AI4 Output
HI_HI alarm occurred
Value and settings of
in the AI4 block.
AI4 HiHi Lim and AI4 Hi
Hi Pri.
Check AI4 Output
LO_LO alarm occurred
Value and settings of
in the AI4 block.
AI4 LoLo Lim and AI4
Lo Lo Pri.
Check AI4 Output
High alarm occurred in
Value and settings of
the AI4 block.
AI4 Hi Lim and AI4 Hi
Pri.
Check AI4 Output
Low alarm occurred in
Value and settings of
the AI4 block.
AI4 Lo Lim and AI4 Lo
Pri.
Check PID Output
HI_HI alarm occurred
Value and settings of
in the PID block.
PID HiHi Lim and PID
Hi Hi Pri.
Check PID Output
LO_LO alarm occurred
Value and settings of
the PID block.
PID LoLo Lim and PID
Lo Lo Pri.
Check PID Output
High alarm occurred in
Value and settings of
the PID block.
PID Hi Lim and PID
Hi Pri.
Check PID Output
Low alarm occurred in
Value and settings of
the PID block.
PID Lo Lim and PID
Lo Pri.
Error Description
Setting error of span
flow rate was detected.
Check or change span
(fulfill "0.05 m/s < span
parameter settings.
flow rate < 16 m/s")
The setting error of
Check the parameter
density value was
settings related to
detected when PV was
density.
set to mass flow rate.
Setting error of pulse
Check Pulse1-related
output 1 was detected.
parameter settings.
Countermeasure
FD bit
7
8
8
8
8
8
8
8
8
Countermeasure
FD bit
3
3
3
IM 01E21A02-03EN
93
0
31
30
29
28
27
26
25
24
23
17
15