YOKOGAWA Admag TI Series User Manual page 172

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Relative
Index
Parameter Name
Index
26
1026
SHED_RCAS
27
1027
SHED_ROUT
28
1028
FAULT_STATE
29
1029
SET_FSTATE
30
1030
CLR_FSTATE
31
1031
MAX_NOTIFY
32
1032
LIM_NOTIFY
33
1033
CONFIRM_TIME 640000
34
1034
WRITE_LOCK
35
1035
UPDATE_EVT
36
1036
BLOCK_ALM
37
1037
ALARM_SUM
38
1038
ACK_OPTION
39
1039
WRITE_PRI
40
1040
WRITE_ALM
Write
Default Value
Mode
640000
AUTO
640000
AUTO
1
-
1
AUTO
1
AUTO
128
-
128
AUTO
AUTO
1
AUTO
0(Uninitialized)
AUTO
0(Uninitialized)
-
0,0
-
0
-
0
-
0(Uninitialized)
AUTO
0(Uninitialized)
-
0,0
-
0(Other)
-
0
-
0x0000
-
0x0000
-
0x0000
-
0x0000
AUTO
0xFFFF
AUTO
0
AUTO
0(Uninitialized)
AUTO
0(Uninitialized)
-
0,0
-
0(Other)
-
0(State 0)
-
<6. Parameter Lists>
Description
Sets time for device's communication
timeout set for Remote cascade. Used
only with PID function.
Sets time for device's communication
timeout set for remote out. Used only
with PID function.
Indicates failsafe state. Not used for this
product.
Starts failsafe state. Not used for this
product.
Resets failsafe state. Not used for this
product.
Maximum number of alert information
which can be held in the device.
Maximum number of alert information
which the device notifies at a time. By
specifying this, the number of alert
to notify the host is limited, and it can
prevent the host from overflowing.
Prohibits setpoints from being written
from the outside.
1: Not Locked
2: Locked
Indicates contents of the event when an
update event (a change to the setpoint)
occurs.
Indicates contents of the alarm when a
block alarm occurs.
Parameter to show the alarm status
of the entire block. Bit assignment
complies with the Communication
standard specifications.
Sets operation to acknowledge
(acknowledgment for the alarm) of
various alarms. By setting a bit to the
alarm, the device operates for the
alarm as if it is acknowledged without
the acknowledgment. Bit assignment
complies with the Communication
standard specifications.
Sets the WRITE_ALM priority. It can be
used not just to set the priority, but to
disable alarm notification with settings.
To activate an alarm on communication,
it is necessary to specify the priority for
alarm activation in advance. To activate
an alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.
The alarm is activated if the write lock
condition is changed in the sequence
like, "Lock -> Reset" or "Reset -> Lock".
171
IM 01E21A02-03EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Admag ti axgAdmag ti axw

Table of Contents