YOKOGAWA Admag TI Series User Manual page 173

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Relative
Index
Parameter Name
Index
41
1041
ITK_VER
COMPATIBILITY_
42
1042
REV
43
1043
CAPABILITY_LEV 0
44
1044
FD_VER
45
1045
FD_FAIL_ACTIVE 0x00000000
FD_OFFSPEC_
46
1046
ACTIVE
FD_MAINT_
47
1047
ACTIVE
FD_CHECK_
48
1048
ACTIVE
49
1049
FD_FAIL_MAP
FD_OFFSPEC_
50
1050
MAP
51
1051
FD_MAINT_MAP 0x000003E0
52
1052
FD_CHECK_MAP 0x01FF8008
53
1053
FD_FAIL_MASK
FD_OFFSPEC_
54
1054
MASK
FD_MAINT_
55
1055
MASK
Write
Default Value
Mode
6
-
2
-
-
1
-
-
0x00000000
-
0x00000000
-
0x00000000
-
0xFC000000
AUTO
0x00003800
AUTO
AUTO
AUTO
0x00000000
AUTO
0x00000000
AUTO
0x00000000
AUTO
<6. Parameter Lists>
Description
Version number of the FF certification
test (interoperability test) by Fieldbus
Foundation applied to this product.
Indicates the lower revision compatible
with the device DevRev.
Indicates capability level inside the
device.
Indicates the major version value of
diagnosis specification of the device.
Parameter assigned to "Failed" by the
NAMUR NE-107 classification. For
details about bit assignment, refer to ■
Field Diagnostic.
Parameter assigned to "Off
Specification" by the NAMUR NE-107
classification. For details about bit
assignment, refer to ■ Field Diagnostic.
Parameter assigned to "Maintenance"
by the NAMUR NE-107 classification.
For details about bit assignment, refer to
■ Field Diagnostic.
Parameter assigned to "Check Function"
by the NAMUR NE-107 classification.
For details about bit assignment, refer to
■ Field Diagnostic.
Specifies a bit to assign to FD_FAIL_
ACTIVE, parameter indicating "Failed",
among 32-bit alarms appearing on
FD_SIMULATE.DiagnosticValue. For
details about bit assignment, refer to ■
Field Diagnostic.
Specifies a bit to assign to FD_
OFFSPEC_ACTIVE, parameter
indicating "Off Specification" among 32-
bit alarms appearing on FD_SIMULATE.
DiagnosticValue. For details about bit
assignment, refer to ■ Field Diagnostic.
Specifies a bit to assign to FD_
MAINT_ACTIVE, parameter indicating
"Maintenance", among 32-bit alarms
appearing on FD_SIMULATE.
DiagnosticValue. For details about bit
assignment, refer to ■ Field Diagnostic.
Specifies a bit to assign to FD_
CHECK_ACTIVE, parameter indicating
"Check Function", among 32-bit
alarms appearing on FD_SIMULATE.
DiagnosticValue. For details about bit
assignment, refer to ■ Field Diagnostic.
Specifies a bit not to notify to the host
among 32-bit "Failed" alarms appearing
on FD_FAIL_ACTIVE. For details
about bit assignment, refer to ■ Field
Diagnostic.
Specifies a bit not to notify to the host
among 32-bit "Off Specification" alarms
appearing on FD_OFFSPEC_ACTIVE.
For details about bit assignment, refer to
■ Field Diagnostic.
Specifies a bit not to notify to the host
among 32-bit "Maintenance" alarms
appearing on FD_MAINT_ACTIVE. For
details about bit assignment, refer to ■
Field Diagnostic.
172