YOKOGAWA Admag TI Series User Manual page 95

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Error Message
NE
107
Display
C
069:Nomi size cfg
C
070:Adh cfg ERR
C
071:FLN cfg ERR
C
072:Log not start
C
247:RB O/S Mode
C
300:AI1 O/S Mode
C
301:AI1 Man Mode
C
302:AI1 Not Schedule
C
303:AI1 Simulate Act
C
304:AI2 O/S Mode
C
305:AI2 Man Mode
C
306:AI2 Not Schedule
C
307:AI2 Simulate Act
C
308:AI3 O/S Mode
C
309:AI3 Man Mode
C
310:AI3 Not Schedule
C
311:AI3 Simulate Act
C
312:AI4 O/S Mode
C
313:AI4 Man Mode
C
314:AI4 Not Schedule
C
315:AI4 Simulate Act
C
328:PID O/S Mode
Error Description
F
OUNDATION
Fieldbus
Configuration error
of nominal size was
detected.
Nominal size
(fulfill "0.99 mm <
configuration error
nominal size of sensor
< 3000.10 mm (0.01
inch < nominal size of
sensor < 120.10 inch)")
Setting error of
electrode adhesion
Adhesion
detection function was
configuration error
detected.
(fulfill "Level1 < Level2
< Level3 < Level4")
Setting error of flow
noise verification
Flow noise
function was detected.
configuration error
(fulfill "Level1 < Level2
< Level3 < Level4")
Data logging not
Data logging failed to
started
start.
Resource block is in
RB in O/S Mode
the O/S mode.
The AI1 block is in the
AI1 in O/S Mode
O/S mode.
The AI1 block is in the
AI1 in Man Mode
Man mode.
AI1 block is
AI1 Not Scheduled
unscheduled.
AI1 Simulation
AI1 simulation function
Active
is running.
The AI2 block is in the
AI2 in O/S Mode
O/S mode.
The AI2 block is in the
AI2 in Man Mode
Man mode.
AI2 block is
AI2 Not Scheduled
unscheduled.
AI2 Simulation
AI2 simulation function
Active
is running.
The AI3 block is in the
AI3 in O/S Mode
O/S mode.
The AI3 block is in the
AI3 in Man Mode
Man mode.
AI3 block is
AI3 Not Scheduled
unscheduled.
AI3 Simulation
AI3 simulation function
Active
is running.
The AI4 block is in the
AI4 in O/S Mode
O/S mode.
The AI4 block is in the
AI4 in Man Mode
Man mode.
AI4 block is
AI4 Not Scheduled
unscheduled.
AI4 Simulation
AI4 simulation function
Active
is running.
The PID block is in the
PID in O/S Mode
O/S mode.
<5. Functions>
Countermeasure
Check the parameter
settings related to
nominal size.
Check the parameter
settings related to
adhesion detection.
Change flow noise
parameter settings.
Insert the microSD
card.
Change it to AUTO
mode.
Change the AI1 block
mode.
Change the AI1 block
mode.
Schedule the AI1 block.
Disable SIMULATE.
Simulate En/Disable of
the AI1 block.
Change the AI2 block
mode.
Change the AI2 block
mode.
Schedule the AI2 block.
Disable SIMULATE.
Simulate En/Disable of
the AI2 block.
Change the AI3 block
mode.
Change the AI3 block
mode.
Schedule the AI3 block.
Disable SIMULATE.
Simulate En/Disable of
the AI3 block.
Change the AI4 block
mode.
Change the AI4 block
mode.
Schedule the AI4 block.
Disable SIMULATE.
Simulate En/Disable of
the AI4 block.
Change the PID block
mode.
IM 01E21A02-03EN
94
FD bit
3
13
3
12
3
11
3
10
1
22
6
31
6
30
6
29
6
28
6
27
6
26
6
25
6
24
6
23
6
22
6
21
6
20
6
19
6
18
6
17
6
16
6
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Admag ti axgAdmag ti axw

Table of Contents