Simulation Function - YOKOGAWA Admag TI Series User Manual

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

5.13

Simulation Function

The product has a function to simulate the input of the function block as if the data is received
from the transducer block. This function makes it possible to test the function block and alarm-
processing system on the downstream side.
To prevent this function from being mistakenly activated while running, a simulation switch is
implemented as a "key" on the amplifier. If this switch (SW1-1) is moved to the ON side, the
simulation is enabled. (See Figure 13.1.) If SIM_ENABLE_MSG of the maintenance transducer
block (index 2922) and REMOTE LOOP TEST SWITCH are written in order to do the same thing
from remote, it activates the same operation as when the above switch is turned ON. However,
the value of this parameter is lost when the power is turned off. An alarm occurs from the
resource block in a state where a simulation is possible. After use, swiftly prohibit simulation.
This function can be configured with the following parameters.
AIFB
Menu path
Display
F
OUNDATION
Fieldbus
*For AXG, one from Al1 to Al4, and for AXW, one from AI1 to AI3.
Block
Relative
Name
Index
AI1 - AI4
(AXG)
9
AI1 - AI3
(AXW)
DIFB
Menu path
Display
F
OUNDATION
Fieldbus
*One from DI1 to DI3.
Block
Relative
Name
Index
DI1 - DI3
9
If "2" is set to Simulate En/Disable, the relevant function block starts using the simulation value
which is set to this parameter instead of the data from the transducer block. It can be used
for propagation of the status to the subsequent block, occurrence of the process alarm, and
operation test of the subsequent block.
--
Diagnostic ► AI1* ► Device Diagnostics ► Service ► (see below)
Parameter
Display
F
OUNDATION
--
Simulation Enable
--
Simulation Disable
--
Diagnostic ► DI1* ► Device Diagnostics ► Service ► (see below)
Parameter
Display
F
OUNDATION
--
Simulate Status
--
Simulate Value
--
Transducer Status
--
Transducer Value
--
Simulate En/Disable
<5. Functions>
Fieldbus
In the communication access
of F
OUNDATION
communication access is set with the
procedures of the interactive operation
guide called DD Method.
Fieldbus
Specifies the data status to simulate.
Specifies the data value to simulate.
Displays the data status from the
transducer block. Unable to change.
Displays the data value from the
transducer block. Unable to change.
Controls the simulation function of this
block.
1: Simulation prohibited (standard
state)
2: Simulation starts
162
Description
Fieldbus, the
Description
IM 01E21A02-03EN