4.6
VFD Parameter Configuration
Set the parameter for function block VFD.
4.6.1

Link object

A link object combines the data voluntarily sent by the function block with the VCR. This product
has 45 link objects. A single link object specifies one combination. Each link object has the
parameters listed in Table 4.6. Parameters must be changed collectively for each VCR because
the modifications made to each parameter may cause inconsistent operation.
Table 4.6
Link Object Parameters
Sub-index
1
LocalIndex
2
VcrNumber
3
RemoteIndex
4
ServiceOperation
5
StaleCountLimit
Forty-five link objects are not set at factory shipping.
Parameter Name
Sets the index of function block parameters to be combined. Set "0"
for Trend and Alert.
Sets the index of VCR to be combined. If set to "0", this link object
is not used.
Not used.
Set to "0".
Set one of the following. Set only one each for link object for Alert
or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
If data is not updated at the time of Subscribe, this is the count
value until the input status is made to Bad. To avoid the careless
mode transition caused when the data is not correctly received by a
subscriber, set this parameter to "2" or more.