YOKOGAWA Admag TI Series User Manual page 265

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Relative
Parameter Name
Index
13
INPUT_OPTS
14
IN
15
IN_LO
16
IN_1
17
IN_2
18
IN_3
19
RANGE_HI
20
RANGE_LO
21
BIAS_IN_1
22
GAIN_IN_1
23
BIAS_IN_2
24
GAIN_IN_2
25
BIAS_IN_3
26
GAIN_IN_3
27
COMP_HI_LIM
28
COMP_LO_LIM
<Appendix 3. Arithmetic (Ar) Block>
Write
Valid
Default
mode
Range
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
+INF
-INF
Description / Remarks
Determines whether an input is used as a "good"
input when the input status is "bad" or "uncertain".
Bit
Function
Handles IN as a "good" status input if its
0
status is "uncertain".
Handles IN_LO as a "good" status input if its
1
status is "uncertain".
Handles IN_1 as a "good" status input if its
2
status is "uncertain".
Handles IN_1 as a "good" status input if its
3
status is "bad".
Handles IN_2 as a "good" status input if its
4
status is "uncertain".
Handles IN_2 as a "good" status input if its
5
status is "bad".
Handles IN_3 as a "good" status input if its
6
status is "uncertain".
Handles IN_3 as a "good" status input if its
7
status is "bad".
8 to
Reserved
15
Input block
Input for a low-range process value.
This is used for the range extension function.
Auxiliary input 1
Auxiliary input 2
Auxiliary input 3
High limit for switching to a high-range process
value (IN) by the range extension function.
Low limit for switching to a low-range process value
(LO_IN) by the range extension function.
IN_1 bias
IN_1 gain
IN_2 bias
IN_2 gain
IN_3 bias
IN_3 gain
High limit of compensation factor f
Low limit of compensation factor f
264