z OUT <= 0
=>OUT_TRIP = 1, OUT_PTRIP = 1
Note that the given conditions do not apply to the following cases:
• If INTEG_TYPE is 5, 6, or 7, OUT_TRIP and OUT_PTRIP always output "0".
• If INTEG_TYPE is 1 or 3, occurrence of AutoRESET (reset caused if the threshold is
exceeded) causes OUT_TRIP to hold "1" for five seconds.
A2.5.3
Mode Handling
Mode
AUTO Normal action
MAN
Integration function is stopped. OUT
will not be updated unless you set a
value to it. No reset is accepted.
O/S
When you rewrite the value in OUT and RTOTAL while at MAN or O/S, N_RESET is
incremented.
Action
Normal output
OUT rewritable. If no value is rewritten, the value with which the
mode was running in AUTO immediately before is held. After
returning to AUTO, integration starts with the written value or
from the value just before running in AUTO.
<Appendix 2. Integrator (It) Block>
Output
248
IM 01E21A02-03EN