4.5.2

Function Block Execution Control

In accordance with the instructions given in Section 4.3, set the execution cycle of the function
blocks and schedule of execution.
4.5.3

Mode Transition

When the function block mode is changed to Out_Of_Service, the function block pauses and a
block alarm is issued.
When the function block mode is changed to Manual, the function block suspends updating of
output values. In this case alone, it is possible to write a value to the OUT parameter of the block
for output. Note that no parameter status can be changed.
Parameter Name
<4. Configuration>
Description
Specifies maximum DL Service Data unit Size (DLSDU).
Set 256 for Server and Trend VCR, and 64 for other VCRs.
Specifies whether connection is monitored. Set TRUE
(0xff) for Server. This parameter is not used for other
communication.
Not used.
Not used.
Not used.
Not used.
Not used.
Indicates VFD of this product to be used. (0x1: System/
network management VFD, 0x1234: Function block VFD)
Set 0 to Server. It is not used for other applications.
Set 1 to Server. It is not used for other applications.
Indicates the type of services in the application layer. In this
product, it is automatically set in accordance with specific
applications.
27
IM 01E21A02-03EN